Function library "LenzeIo1000Drv"
Function blocks
L_io1000ParCounterEPMS602 - Parameterise counter
28 L DMS 1.0 EN - 07/2011 - TD05
4.6 L_io1000ParCounterEPMS602 - Parameterise counter
This FB serves to parameterise the EPM-S602 counter module.
A FALSE/TRUE edge at the bExecute input starts the parameter setting.
The dnState output shows the transmission status.
Inputs
Call possible in: ; Cyclic task
Interrupt task
; Time-controlled task (INTERVAL)
Event-controlled task (EVENT)
L_io1000ParCounterEPMS602
bExecute bDone
dwHandle dnState
byNodeAdr
byAnalogModuleNo
bDiagnosticAlarm
byInputFrequencyTrackA
byInputFrequencyTrackB
byInputFrequencyReset
byAlarmFunction
byCounterFunction
bySignalSelection
bInternalGateInterrupt
byCompareFunction
bInvertDirectionTrackB
byResetFunction
dwLoadValue
dwEndValue
byHysteresis
Identifier/data type Information/possible settings
bExecute
BOOL
FALSEÊTRUE Start parameter setting of the analog output module
dwHandle
DWORD
9400 ServoPLC: Handle created by FB L_CanInit
Drive PLC, 9300 Servo PLC, ECS: 10
byNodeAdr
BYTE
1 ... 127 CAN node address of the I/O system
byAnalogModuleNo
BYTE
1 ... 64 Number of the analog output module
bDiagnosticAlarm
BOOL
TRUE Enable diagnostic alarm