9 RG-MHMET
N2 Points
4.3 Binary Input (BI) Point Descriptions
Point Description
2-01: PID Mode
This point is for monitoring the general state of the drive’s PID mode. If Drive Parameter
#70 (PID Mode) is set to OFF this point returns 0 (DISABLED). If Drive Parameter #70 is set
to either NORMAL or REVERSE, then this point returns 1 (ENABLED).
2-02: Current Direction
This point indicates the direction in which the drive is currently running.
Point Description
2-03: Run / Stop Status
This point indicates whether or not the drive is currently running.
2-04: TB-14 / Relay #2
This point monitors the state of the drive’s TB-14 or Relay #2 output. This point can be
used to indicate various drive conditions as specified by Drive Parameter #52 (TB14/Relay
#2). Refer to the MCH Installation and Operation Manual (MH01) for more information.
2-05: TB-15 / Relay #3
This point monitors the state of the drive’s TB-15 or Relay #3 output. This point can be
used to indicate various drive conditions as specified by Drive Parameter #53 (TB15/Relay
#3). Refer to the MCH Installation and Operation Manual (MH01) for more information.
2-06: Relay #1
This point monitors the state of the drive’s Relay #1 output. This point can be used to
indicate various drive conditions as specified by Drive Parameter #54 (Relay #1). Refer to
the MCH Installation and Operation Manual (MH01) for more information.
2-07: Fault Condition
This point indicates whether or not the drive is currently tripped on a fault. This point
returns 0 (OK) if the drive is not in a fault condition or 1 (FAULT) if it is.
2-08: Serial Watchdog
This point indicates the state of the MCH drive's serial watchdog function. If Drive Parameter
#57 (Serial) is set to WITH TIMER and Point 4-02 is set to NORMAL, then this point returns
a value of 0 (ENABLED). If Drive Parameter #57 (Serial) is set to W/O TIMER or Point 4-02
is set to DISABLE, then this point returns a value of 1 (DISABLED).