Safety instructions
Residual hazards
2
l
30
EDKZN3B024 DE/EN/FR 3.0
2.2 Residual hazards
{ Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Switch off the power supply and wait for at least three minutes
before working on the power terminals.
ƒ Make sure that all power terminals are deenergised.
{ Danger!
Hazardous electrical voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when touching the device in the event of
an error.
Protective measures:
Implement the measures required in EN 61800−5−1. Especially:
ƒ Fixed installation
Implement PE connection in compliance with standards.
Connect PE conductor twice or PE conductor cross−section
³ 10 mm
2
.
ƒ Connection with a connector for industrial applications according
to IEC 60309 (CEE):
PE conductor cross−section ³ 2.5 mm
2
as part of a multi−core
supply cable.
Provide for suitable strain relief.