2Introduction
2.3 Connection to the application
16
Lenze · 8400 protec · Drive-based safety · Software Manual · DMS 2.4 EN · 05/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to decode the I/O status information into single boolean status signals:
1. Go to the I/O level
in the FB editor and connect the wIOState output of the LS_SMInterface
system block with one of the free inputs wFreeIn1 ... wFreeIn4 of the application block.
In the following example, the wIOState output is connected with the free wFreeIn2 input
of the LA_NCtrl application block on the I/O level.
For a better overview, all other connections of the LA_NCtrl application block are not
shown here.
2. Go to the application level
and connect the selected free input wFreeIn with the wIOState
input of the L_SMStateDecoderIO_1 function block.
•The free inputs wFreeIn1 ... wFreeIn4 are outputs on the application level.
The L_SMStateDecoderIO_1 function block decodes the status signal assigned to the
wIOState input into single boolean status signals for further use in the FB interconnection.