Lenze EZN3A0055H045U Manual de usuario Pagina 32

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 70
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 31
Safety instructions
Residual hazards
1
32
EDKZN3B045 DE/EN/FR 3.0
Danger!
Hazardous electrical voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when touching the device in the event of
an error.
Protective measures:
Implement the measures required in EN 61800−5−1. Especially:
ƒ Fixed installation
Implement PE connection in compliance with standards.
Connect PE conductor twice or PE conductor cross−section
³ 10 mm
2
.
ƒ Connection with a connector for industrial applications according
to IEC 60309 (CEE):
PE conductor cross−section ³ 2.5 mm
2
as part of a multi−core
supply cable.
Provide for suitable strain relief.
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ Observe the maximally permissible mains voltage.
ƒ Fuse the device correctly on the supply side against mains
fluctuations and voltage peaks.
Vista de pagina 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 69 70

Comentarios a estos manuales

Sin comentarios