Electrical installation
Wiring of system bus (CAN)
4
104
EDKCSEE040 DE/EN/FR 4.0
Bus cable length
Note!
Thepermissiblecablelengthsmustbeobserved.
1. Check the compliance with the total cable length in Tab. 4-1.
The baud rate determines the total cable length.
CAN baud rate [kbit/s] Max. bus length [m]
50 1500
125 630
250 290
500 120
1000 25
Tab. 4-1 Total cable length
2. Check the compliance with the segment cable length in Tab. 4-2.
The segment cable length is determined by the cable cross-section used and the
number of nodes. Without a repeater, the segment cable length corresponds to
thetotalcablelength.
Number of nodes
Cable cross-section
0.25 mm
2
0.5 mm
2
0.75 mm
2
1.0 mm
2
2 240 m 430 m 650 m 940 m
5 230 m 420 m 640 m 920 m
10 230 m 410 m 620 m 900 m
20 210 m 390 m 580 m 850 m
32 200 m 360 m 550 m 800 m
63 170 m 310 m 470 m 690 m
Tab. 4-2 Segment cable length
3. Compare the two values detected.
If the value detected from Tab. 4-2 is smaller than the total cable length to be
providedfrom Tab. 4-1, repeaters mustbe used. Repeaters dividethe total cable
length into segments.