Technical Data
UONu_^MPMQ 3-5
L
8218821782168215Type150 % overload
EVF8218-EEVF8217-EEVF8216-EEVF8215-EOrder no.
8218-V0038217-V0038216-V0038215-V003TypeVariant ”Cold
Plate”
EVF8218-C-
V003
EVF8217-C-
V003
EVF8216-C-
V003
EVF8215-C-
V003
Order no.
Variant ”Cold
Plate”
Motor voltage
3)
V
motor
[V] 0-3× V
mains
/0Hz¼ 50Hz, if required up to 480Hz
Power loss (operation with I
Nx
) P
loss
[W] 150 200 280 400
Power reduction [%/K]
[%/m]
40 °C<T
amb
<50°C: 2.5%/K
1000 m a.m.s.l
< h ≤ 4000 m a.m.s.l: 5 %/1000 m
Field
Resolution absolute 0.02 Hz
frequency
Digital setpoint
selection
Accuracy 0.05 Hz
Analog setpoint
Linearity 0.5 % (max. selected signal level: 5 V or 10 V)
selection
Temperature
sensitivity
0 ¼ 40 °C: +0.4 %
Offset 0%
Weight
”Cold Plate” without heat sink
”Cold Plate” with heat sink
m[kg] 5.3
2.8
20.8
5.3
2.8
20.8
5.3
2.8
20.8
5.3
2.8
20.8
Printed in bold Data for the operation with factory setting and a chopper frequency of 8 kHz.
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here
and 2 minutes base load with 75% I
Nx
.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
* Chopper frequency of the inverter