LDCDS−EL100.LRNÄ.LRNäOperating InstructionsHMI with Windowsâ CE EL 1xx ECO, EL 1xx ECO PLC, EL 1xx CAN, EL 1xx PLC, EL 1xx MPIHMI for visualisation /
Safety instructionsGeneral safety instructions2 10LDCDS−EL100 EN 9.02 Safety instructions2.1 General safety instructions Danger!Disregarding
Safety instructionsGeneral safety instructions2 11LDCDS−EL100 EN 9.0Mechanical installationƒ Install the product according to the regulation
Safety instructionsProduct−specific safety instructions2 12LDCDS−EL100 EN 9.0Disposalƒ Recycle metals and plastic materials. Ensure profession
Safety instructionsSafety instructions for the installation according to UL2 13LDCDS−EL100 EN 9.0 2.3 Safety instructions for the installati
Safety instructionsSafety instructions for the installation according to UL2 14LDCDS−EL100 EN 9.0HomologationUnderwriter Laboratories (UL), U
Product descriptionApplication as directed3 15LDCDS−EL100 EN 9.03 Product description3.1 Application as directed HMIs of the EL 1xx seriesƒ
Product descriptionScope of supplyEL 1xx CAN/PLC/MPI3 16LDCDS−EL100 EN 9.0 3.2 Scope of supplyNumber Description1 HMI44468Screw clamp fixingsf
Product descriptionOverviewEL 1xx ECO (PLC)3 17LDCDS−EL100 EN 9.0 3.3.2 EL 1xx ECO (PLC)EL100e−001Pos. Description HMI Screw clamp fixings
Technical dataGeneral data and operating conditions4 18LDCDS−EL100 EN 9.04 Technical data4.1 General data and operating conditions Conformit
Technical dataElectrical dataEL 1xx CAN/PLC/MPI4 19LDCDS−EL100 EN 9.0 4.2 Electrical data4.2.1 EL 1xx CAN/PLC/MPISupplyType EL xxx105m 105 1
Please read these instructions before you start working!Follow the enclosed safety instructions.
Technical dataElectrical dataEL 1xx CAN/PLC/MPI4 20LDCDS−EL100 EN 9.0ScreenTyp EL xxx105m 105 106Type Touch screen, resistiveColours 16 grey t
Technical dataElectrical dataEL 1xx CAN/PLC/MPI4 21LDCDS−EL100 EN 9.0PLC functions (EN 61131−3)Typ EL xxx PLC105m 105 106 108 110 110sEditor
Technical dataElectrical dataEL 1xx ECO (PLC)4 22LDCDS−EL100 EN 9.04.2.2 EL 1xx ECO (PLC)SupplyType EL xxx ECO103Voltage [V] DC 24 (+18 ... 30
Technical dataElectrical dataEL 1xx ECO (PLC)4 23LDCDS−EL100 EN 9.0ScreenTyp EL xxx ECO103Type Touch screen, resistiveColours 64 KDisplay di
Technical dataMechanical dataEL 1xx CAN/PLC/MPI4 24LDCDS−EL100 EN 9.0 4.3 Mechanical data 4.3.1 EL 1xx CAN/PLC/MPIDesign and weightType EL x
Technical dataMechanical dataEL 1xx ECO (PLC)4 25LDCDS−EL100 EN 9.04.3.2 EL 1xx ECO (PLC)Design and weightType EL xxx ECO103Front Aluminium
Mechanical installationImportant notes5 26LDCDS−EL100 EN 9.05 Mechanical installation5.1 Important notesThe installation must be carried out b
Mechanical installationMounting steps5 27LDCDS−EL100 EN 9.05.2 Mounting stepsEL100−004How to assemble the HMI:1. Cut the mounting cutout out
Electrical installationImportant notes6 28LDCDS−EL100 EN 9.06 Electrical installation6.1 Important notesThe installation must be carried out b
Electrical installationWiring according to EMC6 29LDCDS−EL100 EN 9.06.2 Wiring according to EMCGeneral notes l The electromagnetic compatibi
Contents i 3LDCDS−EL100 EN 9.01 About this documentation 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical installationWiringEL 1xx CAN/PLC/MPI6 30LDCDS−EL100 EN 9.0 6.3 Wiring6.3.1 EL 1xx CAN/PLC/MPIMains connection Note!ƒ Observe the m
Electrical installationWiringEL 1xx CAN/PLC/MPI6 31LDCDS−EL100 EN 9.0 Serial interfaceDescription Connection type Cable type61RS232 connecti
Electrical installationWiringEL 1xx CAN/PLC/MPI6 32LDCDS−EL100 EN 9.0CAN interface Note!ƒ Only connect terminals of the same signal type.ƒ Fo
Electrical installationWiringEL 1xx CAN/PLC/MPI6 33LDCDS−EL100 EN 9.0MPI interface Note!ƒ For more information on the MPI port, please see
Electrical installationWiringEL 1xx ECO (PLC)6 34LDCDS−EL100 EN 9.06.3.2 EL 1xx ECO (PLC)Mains connectionEL100e−005Description Connection type
Electrical installationWiringEL 1xx ECO (PLC)6 35LDCDS−EL100 EN 9.0USB interfaceDescription Connection type Cable typeUSB 2.0 host connectio
Electrical installationWiringEL 1xx ECO (PLC)6 36LDCDS−EL100 EN 9.0Description Connection type Cable typeCAN bus connectionPin 1: CAN−GND (CG)
CommissioningConnecting external devices7 37LDCDS−EL100 EN 9.07 Commissioning 7.1 Connecting external devicesThe HMI can communicate with o
CommissioningInitial switch−on7 38LDCDS−EL100 EN 9.07.2 Initial switch−onHow to proceed:1. Check the whole wiring for completeness and correct
CommissioningEstablish Ethernet connectionConfigure Ethernet interface7 39LDCDS−EL100 EN 9.07.3.1 Configure Ethernet interfacePrerequisite:
Contentsi 4LDCDS−EL100 EN 9.07 Commissioning 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CommissioningEstablish Ethernet connectionActivate communication between EL 1xx and VisiWinNetâ Smart7 40LDCDS−EL100 EN 9.07.3.2 Activate comm
CommissioningEstablish CAN fieldbus connectionConfigure CAN interface7 41LDCDS−EL100 EN 9.07.4 Establish CAN fieldbus connectionAn EL 1xx CA
CommissioningEstablish MPI connection7 42LDCDS−EL100 EN 9.07.5 Establish MPI connectionAn EL1xx MPI is able to communicate with a S7 PLC via M
CommissioningUPS functionality7 43LDCDS−EL100 EN 9.07.6 UPS functionalityAn "EL 1xx PLC" is equipped with an internal UPS which −
CommissioningInstalling fonts7 44LDCDS−EL100 EN 9.07.7 Installing fontsIf you want to use additional fonts, for instance containing Asian char
OperationOperating system components8 45LDCDS−EL100 EN 9.08 Operation 8.1 Operating system componentsThe following table shows the component
OperationControl Panel Applets8 46LDCDS−EL100 EN 9.08.2 Control Panel AppletsThe Control Panel Applets adjusted or advanced by LENZE are descr
OperationControl Panel AppletsStartUp8 47LDCDS−EL100 EN 9.08.2.1 StartUpEL100−023 Show Explorer: After the booting, the Windows CE desktop
OperationControl Panel AppletsRegistry8 48LDCDS−EL100 EN 9.08.2.2 Registry Note!The modifications of some Applets are automatically stored in
OperationControl Panel AppletsVisiWinNETâ8 49LDCDS−EL100 EN 9.08.2.3 VisiWinNETâEL100−025 Startup Project: Display of the VisiWinNETâ start
Contents i 5LDCDS−EL100 EN 9.08.5 Communicating via the CAN gateway function 78. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.5
OperationControl Panel AppletsServer8 50LDCDS−EL100 EN 9.08.2.5 ServerEL100−027Find more information later in this chapter ( 72). 8.2.6 Fie
OperationControl Panel AppletsMPI Configuration8 51LDCDS−EL100 EN 9.08.2.7 MPI ConfigurationEL100−029This Applet is only relevant for an EL
OperationControl Panel AppletsCAN Gateway8 52LDCDS−EL100 EN 9.0"State" registerEL100−032Gateway: Start and stop gateway functionBus
OperationControl Panel AppletsCAN Gateway8 53LDCDS−EL100 EN 9.0 "CAN" registerEL100−034Parameter channel: The parameter channel fo
OperationControl Panel AppletsCAN Gateway8 54LDCDS−EL100 EN 9.0"Logging" registerThis register displays errors that may be pending.E
OperationCreating a PLC sample programGeneral information on PLC programming8 55LDCDS−EL100 EN 9.08.3 Creating a PLC sample program The foll
OperationCreating a PLC sample programStart PLC Designer8 56LDCDS−EL100 EN 9.08.3.2 Start PLC Designer How to proceed:1. With a standard insta
OperationCreating a PLC sample programCreate PLC program8 57LDCDS−EL100 EN 9.04. Enable the General register and select the Download symbol
OperationCreating a PLC sample programCreate PLC program8 58LDCDS−EL100 EN 9.08. Enter the word "Count" in the lower half of the div
OperationCreating a PLC sample programCreate PLC program8 59LDCDS−EL100 EN 9.012. Enter the following code in the lower half of the divided
About this documentationValidity information1 6LDCDS−EL100 EN 9.00Fig. 0Tab. 01 About this documentation1.1 Validity informationThese instruct
OperationCreating a PLC sample programCreate sym file8 60LDCDS−EL100 EN 9.08.3.4 Create sym file A sym file is required if the visualisation,
OperationCreating a PLC sample programCreate sym file8 61LDCDS−EL100 EN 9.04. Select the Export variables of object control field in the &qu
OperationCreating a PLC sample programTransfer program to HMI8 62LDCDS−EL100 EN 9.08.3.5 Transfer program to HMI How to proceed:1. Go to the m
OperationCreating a PLC sample programTransfer program to HMI8 63LDCDS−EL100 EN 9.04. Click OK to close the dialogue.After this, the "C
OperationCreating a PLC sample programStart program on HMI8 64LDCDS−EL100 EN 9.08.3.6 Start program on HMI How to proceed:1. Go to the menu ba
OperationCreating a PLC sample programBuild up CAN communication with distributed I/O module8 65LDCDS−EL100 EN 9.07. Right−click the Explore
OperationCreating a PLC sample programBuild up CAN communication with distributed I/O module8 66LDCDS−EL100 EN 9.09. For this, right−click the
OperationCreating a PLC sample programBuild up CAN communication with distributed I/O module8 67LDCDS−EL100 EN 9.012. Go to the POUs registr
OperationCreating a PLC sample programBuild up CAN communication with distributed I/O module8 68LDCDS−EL100 EN 9.013. For this, go to the Reso
OperationCreating a PLC sample programBuild up CAN communication with distributed I/O module8 69LDCDS−EL100 EN 9.015. Go to the Resources re
About this documentationDocument history1 7LDCDS−EL100 EN 9.01.3 Document historyMaterial number Version Description.LRN 9.0 11/2013 TD29 Sa
OperationCreating a PLC sample programBuild up CAN communication with distributed I/O module8 70LDCDS−EL100 EN 9.018. Assign the node address
OperationAccess EL 1xx via server functionality8 71LDCDS−EL100 EN 9.08.4 Access EL 1xx via server functionalityVarious servers are integrate
OperationAccess EL 1xx via server functionalityEnable Server Access8 72LDCDS−EL100 EN 9.08.4.1 Enable Server Access Before the servers of the
OperationAccess EL 1xx via server functionalityEnable Server Access8 73LDCDS−EL100 EN 9.0Enter the password for accessing the server The ac
OperationAccess EL 1xx via server functionalityFTP Server − Transmit Data8 74LDCDS−EL100 EN 9.08.4.2 FTP Server − Transmit Data The access to
OperationAccess EL 1xx via server functionalityTelnet Server − Manage files at the Windows Command Prompt8 75LDCDS−EL100 EN 9.08.4.4 Telnet
OperationAccess EL 1xx via server functionalityVNC−Server − Operate the EL 1xx by remote control via Internet or LAN8 76LDCDS−EL100 EN 9.08.4.
OperationAccess EL 1xx via server functionalityRAS Server − Operate your EL 1xx by remote control via telephone line8 77LDCDS−EL100 EN 9.08.
OperationCommunicating via the CAN gateway functionImportant notes8 78LDCDS−EL100 EN 9.08.5 Communicating via the CAN gateway function8.5.1 Im
OperationCommunicating via the CAN gateway functionEstablishing communication using the system bus configurator8 79LDCDS−EL100 EN 9.0Adding
About this documentationConventions used1 8LDCDS−EL100 EN 9.01.5 Conventions usedType of information Identification Examples/notesSpelling of
OperationCommunicating via the CAN gateway functionEstablishing communication using the system bus configurator8 80LDCDS−EL100 EN 9.0 Note!Al
OperationCommunicating via the CAN gateway functionEstablishing communication using the system bus configurator8 81LDCDS−EL100 EN 9.0EL100−0
OperationCommunicating via the CAN gateway functionEstablishing communication using the Global Drive Control (GDC)8 82LDCDS−EL100 EN 9.0 8.5.3
OperationCommunicating via the CAN gateway functionEstablishing communication using the Global Drive Control (GDC)8 83LDCDS−EL100 EN 9.0EL10
OperationCommunicating via the CAN gateway functionEstablishing communication using the L−force Engineer8 84LDCDS−EL100 EN 9.0 8.5.4 Establish
OperationCommunicating via the CAN gateway functionEstablishing communication using the L−force Engineer8 85LDCDS−EL100 EN 9.0EL100−0457. Cl
OperationCommunicating via the CAN gateway functionEstablishing communication using the L−force Engineer8 86LDCDS−EL100 EN 9.0EL100−04710. Set
OperationCommunicating via the CAN gateway functionEstablishing communication using the Drive PLC Developer Studio (DDS)8 87LDCDS−EL100 EN 9
OperationCommunicating via the CAN gateway functionEstablishing communication using the Drive PLC Developer Studio (DDS)8 88LDCDS−EL100 EN 9.0
MaintenanceGeneral notes9 89LDCDS−EL100 EN 9.09 Maintenance9.1 General notes Stop!Short circuit and static dischargeThe device contains co
About this documentationNotes used1 9LDCDS−EL100 EN 9.0 1.6 Notes usedThe following pictographs and signal words are used in this documentat
MaintenanceCleaning9 90LDCDS−EL100 EN 9.09.3 Cleaning Stop!Sensitive surfaces and componentsThe device can be damaged if it is not appropriat
MaintenanceBattery replacement9 91LDCDS−EL100 EN 9.09.4 Battery replacement Danger!Danger of fire and explosionOn the baseboard there is a
MaintenanceBattery replacement9 92LDCDS−EL100 EN 9.0 How to proceed:1. Remove all connected cables and the SD card.2. Remove the device and pu
Index 10 93LDCDS−EL100 EN 9.010 IndexAAddFont.exe, 44Ambient conditions− climatic, 18− Shock, 18− Vibration, 18Applet− CAN Gateway Config
Index10 94LDCDS−EL100 EN 9.0Interface− CAN, 41− LAN, 38− MPI, 42LLAN connection, 31, 34LAN interface, 38MMains connection, 30, 34Mainte
Index 10 95LDCDS−EL100 EN 9.0TTechnical data, 18− Electrical data, 19− mechanical data, 24Telnet Server, 75Type of protection, 18UUninte
© 11/2013FLenze Automation GmbHHans−Lenze−Str. 1D−31855 AerzenGermanyService Lenze Service GmbHBreslauer Straße 3D−32699 ExtertalGermany(+49(0)51