18 DESCRIPTION OF PARAMETERS
0 LINE VOLTS
This parameter calibrates the drive based on the input voltage, and can be set to AUTO,
HIGH, or LOW. When set to AUTO, the drive automatically selects HIGH or LOW based
on the incoming voltage.
This parameter can also be set “manually”, using the HIGH or LOW settings. Refer to
the Input Line Voltage table herein.
INPUT LINE VOLTAGE SELECTION
MODEL
RATED INPUT
VOLTAGE
INPUT
PHASE
ACTUAL INPUT
VOLTAGE
PARAM.
SETTING
MH200 240 / 200 Vac 3 220 - 240 Vac HIGH
240 / 200 Vac 3 200 - 208 Vac LOW
MH400 480 / 400 Vac 3 460 - 480 Vac HIGH
480 / 400 Vac 3 380 - 415 Vac LOW
MH500 590 / 480 Vac 3 575 - 600 Vac HIGH
590 / 480 Vac 3 460 - 480 Vac LOW
1-4 PRESET #1- #4
PRESETS are activated via contact closures between terminal TB-2 and terminals TB-
13A, TB-13B and TB-13C. These terminals must be programmed as preset selects
using Parameters 47 - 49: TB13A INPUT, TB13B INPUT, and TB13C INPUT.
In non-PID mode, PRESETS #1-#4 can be used as preset speeds. In this case, the
PRESETS are set in Hz, and can only be set to values within the range dened by the
minimum and maximum frequency (Parameters 10 and 11).
In PID mode, PRESETS #1, #2 and #4 can also be used as preset setpoints (PRESET
#3 cannot be used as a preset setpoint, only a preset speed). In this case, PRESETS
#1, #2 and #4 are set in actual PID units (the units selected in Parameter 31 - UNITS),
and can only be set to values within the range dened by the minimum and maximum
PID feedback (Parameters 75 and 76).
The Preset Activation table shows how each preset is selected using the TB-13
terminals. OPEN and CLOSED refer to the state of the TB-13 terminal relative to TB-2.
PRESET ACTIVATION
PRESET # TB - 13A TB - 13B TB - 13C
1 CLOSED OPEN OPEN
2 OPEN CLOSED OPEN
3 OPEN OPEN CLOSED
CLOSED CLOSED OPEN
4 CLOSED OPEN CLOSED
OPEN CLOSED CLOSED