Function library Lenze8200Drive.lib
Introduction
2−2
l
Lenze8200Drive.lib EN 1.0
2.2 Frequency inverter parameterisation
When the program is started, the parameter data shall be written only once during initialisation to
the frequency inverter. The FBs L_8200Parameter and L_8200Initialization therefore have to be
called in the system task PLC_PRG.
· The FB L_8200Parameter is used to initialise the codes with the corresponding values.
· After this, the FB L_8200Initialization is used to transfer the parameters to the individual
frequency inverters.
L_8200Parameter
L_8200Initialization
L_8200Initialization
L_8200Initialization
node id = x
node id = y
node id = z
L
8200
node id = x
L
8200
L
8200
node id = y node id = z
PLC_PRG
C0011 = ...
C0012 = ...
C0013 = ...
C0127 = ...
C0356 = ...
C0410 = ...
...