Communication manual 8400 motec PROFIBUS
Error messages
Possible causes and remedies
80 L EDS84DMOTPBUS EN 3.0 - 11/2011
Profibus Watchdog: Monitoring time elapsed [0x01bc8130]
Profibus: State Data_Exchange left [0x01bc8131]
Profibus Watchdog: DP-V1 MSC2 elapsed [0x01bc8132]
Response (Lenze setting printed in bold) Setting: C13880/1 (; adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Permanent interruption of communication to PROFIBUS
master.
See also chapter "Permanent interruption of
PROFIBUS communication" ( 69).
Check cables and terminals.
Note:
We recommend to set "Warning locked" for the response
(no drive-relevant response).
Response (Lenze setting printed in bold) Setting: C13880/1 (; adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Data exchange via PROFIBUS has been stopped.
See also chapter "Permanent interruption of
PROFIBUS communication" ( 69).
Check cables and terminals.
The slave must receive new parameterisation and
configuration files from the master in order to be able to
exchange data again.
Response (Lenze setting printed in bold) Setting: C13880/2 (; adjustable response)
: No response System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Permanent interruption of communication to PROFIBUS
master.
See also chapter "Permanent interruption of
PROFIBUS communication" ( 69).
Check cables and terminals.
Note:
We recommend to set "Warning locked" for the response
(no drive-relevant response).