
6 Commissioning of the PROFINET
6.1 Overview of the commissioning steps
20
Lenze · Controller-based Automation · PROFINET® Communication Manual · DMS 1.2 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6 Commissioning of the PROFINET
This chapter provides information on how to commission the Lenze automation system with
PROFINET.
Depending on the field devices used, the following Lenze Engineering tools
( 17) are required:
• »EASY Starter«
• »Engineer«
•»PLC Designer«
6.1 Overview of the commissioning steps
The main commissioning steps are listed in the following table.
Note!
• In the Lenze automation system, no PROFINET master functionality is supported. In a
PROFINET network, a Lenze Controller can only be driven as I/O device (slave), e.g. by
a Siemens SIMATIC S7 PLC.
• In the Lenze automation system, Logic field devices can be exclusively operated via
PROFINET. Thus, as an I/O device, the Lenze Controller is a Logic field device.
• The motion functionality is not supported when PROFINET is used. Always use
EtherCAT to connect inverters to be controlled via the central Motion functionality.
Mixed operation PROFINET with EtherCAT
( 32)
Step Activity Software to be used
1st Planning the bus topology
( 21)
2nd Installing field devices
( 21)
3rd Create a project folder ( 22)
4th Commissioning the field devices
( 22) »Engineer«/»EASY Starter«
If necessary Importing missing devices / device description files
( 23)
»STEP7«
5th Creating a PLC program with a target system (Logic)
( 24) »PLC Designer«
6. Configuring the communication parameters ( 26)
7. Creating a control configuration (adding field devices)
( 28)
8. Configuring the I/O device
( 31)
9. Logging in on the controller with the »PLC Designer«
( 31)
With the log-in, the I/O device configuration is loaded into the
controller.
Comentarios a estos manuales